Gammapilot M FMG60 FOUNDATION Fieldbus
Operation
Hauser
45
Parameter
Parameter
Description
TAG_DESC
User description of the intended application of the block
MODE_BLK
Lists the actual, target, permitted and normal operating modes of the block.
• Target: changes the operating mode of the block
• Actual: indicates the current operating mode of the block
• Permitted: shows which operating modes are allowed
• Normal: indicates the normal operating mode of the block
The possible operating modes of the Resource block are:
• AUTO: the block is operating as normal
• OOS: the block is out of service
If the Resource block is out of service, then all other device blocks are also set to this mode
RS_STATE
Indicates the state of the Resource block application state machine
• On-line: the block is in AUTO mode
• Standby: the block is in the OOS mode
WRITE_LOCK
Indicates the setting of the WP DIP switch
• LOCKED: device data cannot be modified
• NOT LOCKED: device data can be modified
RESTART
Enables a manual restart
• UNINITIALISED: no status
• RESOURCE: resets the Resource block parameters
• DEFAULTS: resets all Foundation Fieldbus parameters in the device, but does not reset the
manufacturer-specific parameters
• PROCESSOR: perform a processor warm start
BLOCK_ERROR Indicates the error status of software and hardware components
• Out-of-Service: the block is in the OOS mode
• Simulation active: indicates the setting of the SIM DIP switch
BLOCK_ALM
Shows any configuration, hardware, connection and system problems in the block. The cause
of the alarm is displayed in the subcode field.
The functions of the Resource block not described here can be found in the Foundation
Fieldbus Specification, see "
www.fieldbus.org
".
6.6.6
Transducer block
E+H_GAMMAPILOT_M_XXXXXXXXXXX
.....RESOURCE_XXXXXX (RB2)
.....
TRANSDUCER_XXXXXX (TBUL)
.....ANALOG_INPUT_1_XXXXXX (AI)
Operation
The Transducer block contains the parameters required to calibrate the device. These
parameters can also be read out and edited using the VU331 display module. The
calibration of the device is described in,
"Commissioning"
. The Transducer block is opened
by clicking the "Transducer " line. Parameter changes using the tool are made offline. The
device can remain in operation during this time.
The changes are downloaded to the device by first setting MODE_BLK = OOS and then
pressing the WRITE CHANGES button. If you want to check all the values saved in the
device, click READ ALL. To return to operation, set the MODE_BLK to AUTO.
2)
If it is not possible to set MODE_BLK to AUTO, an error has occurred. Should this happen, check all the parameters, make the necessary changes
and try to set MODE_BLK to AUTO again