Commissioning
Gammapilot M FMG60 FOUNDATION Fieldbus
56
Hauser
7.1.1
Basic setup
Step Function
Entry or selection
Comments
See page
1
Present date (*01)
Sample value:
12.11.04 10:30
Set the day with and ; confirm with ;
the same routine applies for the month, year,
hour and minute
2
Beam type (*02)
• Standard/cont.
• Modulated
Select with and ; confirm with
3
Isotope (*03)
•
137
Cs
•
60
Co
• No compensation
Select with and ; confirm with
4
Operating mode (*04)
• Stand alone
• Master
• Slave
• End slave
• Not defined
Select with and ; confirm with
5
Measurement mode
(*05)
• Level
• Switch
• Density
• Concentration
Select with and ; confirm with
The following functions are for density and concentration measurements only:
6
Density unit (*06)
• g/cm
3
• g/l
• ...
Select with and ; confirm with
7
Min. density (*07)
(lower limit of the
measuring range)
Sample value:
0.9500 g/cm
3
Set each decimal place with and and
confirm with ; after the last place, confirm
the whole value with .
8
Max. density (*08)
(upper limit of the
measuring range)
Sample value:
1.2500 g/cm
3
Set each decimal place with and and
confirm with ; after the last place, confirm
the whole value with .
9
Pipe diameter unit
(*09)
• mm
• inch
Select with and ; confirm with
10
Pipe diameter (*0A)
Sample value:
200 mm
Set each decimal place with and and
confirm with ; after the last place, confirm
the whole value with .
The following function is for all measurement modes:
11
Output damping (*0B)
Sample value:
60 s
Set each decimal place with and and
confirm with ; after the last place, confirm
the whole value with .
7.1.2
Calibration for level measurement and point level detection
The general principles for calibrating for level measurement and point level detection
are described in "Calibration for level measurement and point level detection"
Background calibration
For details refer to "Background calibration"
Step
Function
Action/comments
1
• Switch off radiation
• Fill vessel
For level: min. 60%
For switch (level limit): radiation path is covered
2
Background calibration (*10)
Select "Start" with or ; confirm with
3
Avg. pulse rate (*11)
Wait until the value is stable, then confirm with
4
Background calibration (*10)
Select "Stop/edit" with or ; confirm with