Gammapilot M FMG60 FOUNDATION Fieldbus
Operation
Hauser
53
Alarm priorities
Parameter
Description
0
The alarm is suppressed
1
Is recognized by the system but is not reported
2
Is reported to the operator but does not require the operator's attention
3-7
Advisory alarms of increasing priority
8-15
Critical alarms of increasing priority
Alarm status
Parameter
Description
HI_HI_ALM
Status of the HI_HI alarm
HI_ALM
Status of the HI alarm
LO_ALM
Status of the LO alarm
LO_LO_ALM
Status of the LO_LO alarm
Simulation
The SIMULATE parameter makes it possible to simulate the output value of the
Transducer block provided that the simulation has also been enabled at the DIP switch of
the device. The simulation must be enabled, the value and/or status must be entered and
the block must be in AUTO mode. During simulation the Transducer block output value is
substituted by the simulated value. A simulation is also possible by switching MODE_BLK
to "MAN" and entering a value for OUT.
Parameter
Description
SIMULATE
Enables, sets and displays a simulated value; options
• Enable/disable
• Simulated value
• Output value
6.6.10 Commissioning checklist
The following checklist refers to the configuration using the NI-Fieldbus Configurator.
Generally speaking, the procedure is similar for other network configuration tools.
1. Configure the network and integrate the device
•Identify the device using the device ID and serial number
•If necessary, assign a new PD_TAG
2. Configure the Resource block
•Check the position of the hardware switch in WRITE_LOCK
•If "locked" is displayed, change the position of the DIP switch
•If necessary, change the block tag (right-click the tree)
•Set MODE_BLK_TARGET to Out-of-Service
•Reset the device to the factory settings with the function RESTART Þ Defaults
(this function can also be accessed by right-clicking the device name)
•If necessary, assign a new tag description (TAG_DESC)
•Set MODE_BLK_TARGET to AUTO