Commissioning
Gammapilot M FMG60 FOUNDATION Fieldbus
64
Hauser
1
1
1
L
L
L
a
D
I
a
L
30° 2.0 x D
I
A0018109
8
Always specify the complete irradiated measuring path L in the "Pipe diameter" (*0A) function. Depending
on the installation, this value may be larger than the actual pipe diameter.
1
Gammapilot M
7.3.11 "Output damping" (*0B)
Local display
Output damping *0B
60 s
This function is used to specify the output damping time τ (in seconds). A change in the
measured value is attenuated by this time. After a change in the level or density it takes 5
x τ until the new measured value is reached.
5 x
t
t
L
1
2
A0018110
1
Level change (or density change)
2
Measured value
Value range
1 to 999 s