Gammapilot M FMG60 FOUNDATION Fieldbus
Wiring
Hauser
31
5.8
Wiring in connection compartment 1
L
CAUTION
Note the following before connecting:
‣
If the device is used in hazardous areas, make sure to comply with national standards
and the specifications in the Safety Instructions (XAs). The specified cable gland must
be used.
‣
The supply voltage must match the specifications on the nameplate
‣
Switch off the supply voltage before connecting the device.
‣
Connect the potential matching line to the external ground terminal of the transmitter
and to the ground terminal of the water cooling jacket (if present) before connecting
‣
Connect the protective ground to the protective ground terminal → 27
‣
According to IEC/EN 61010 a suitable circuit breaker must be provided for the device
‣
The cables must be adequately insulated, with due consideration given to the supply
voltage and the overvoltage category.
‣
The connecting cables must offer adequate temperature stability, with due
consideration given to the ambient temperature.
1
L1
L+
+
-
N
L-
A0019826
1. Using a 3 mm Allen key, loosen the cover clamp for the connection compartment
cover
2. Unscrew the cover
3. Push the power cable and (if required) the signal cable through the appropriate cable
glands or cable entries
4. Wire up according to the terminal assignment diagram
5. Tighten the cable glands or cable entries so that they are leak-tight
6. Screw the cover securely back onto the connection compartment
7. Turn the cover clamp so that it is set over the cover and then tighten.