background image

ELECTRICITY METER LEM-40

DIGITAL - THREE-PHASE

 

USER’S MANUAL

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04

www.zamel.com

, e-mail: [email protected]

lem-40_inst_ext_gb | 10.02.21

FEATURES

TECHNICAL DATA

DESCRIPTION

APPEARANCE

Power supply terminals: top - inputs (IN): L1, L2, L3, N

bottom - outputs (OUT): L1, L2, L3, N

Reference voltage: 3 x 230 V / 400 V AC

Voltage tolerance: -15 ÷ +10 %

Rated frequency: 50 / 60 Hz

Base current (Ib): 3 x 10 A

Maximum current (Imax): 100 A

Operating current range: 0,4% I

b

 ÷ I

max

Current overload: 30x I

max

 for 0,01 s

Meter own consumption: 10 VA / 2 W 

Accuracy of measurement (IEC61036): class B (class 1)

Display: Counter 6+2 digits

Indication for pulse counting: red LED

Pulse output SO+ SO-: OC type, terminals: 22 (-), 23 (+)

Connection voltage SO+ SO-: 5 ÷ 27 V DC

SO+ SO- connection current: < 27 mA

SO+ SO- contant: 1000 pulses per kWh

Pulse time SO+ SO-: 30 ms

Number of connection terminals: 10

Cross-section of connection cables: main connection: 4 ÷ 25 mm

2

pulse output: minimum 0.2 mm

2

Operating temperature: -25 ÷ +55 

o

C

Enclosure mounting: TH 35 rail (according to EN 60715)

Enclosure IP rating: IP51

Overvoltage category: II

Contamination degree: 2

Dimensions: 72 x 100 x 66 mm

Weight: 0,700 kg

●  Three-phase digital energy meter,

●  Class B (equivalent to class 1),

●  Maximum current of the meter: 100A,

●  6+2 LCD display,

●  Additional pulse output,

●  Indication for pulse counting,

●  Signalling  the  presence  of  voltage  of  each 

phase,

●  Sealable terminal covers,

●  Installation on TH 35 rail.

The LEM-40 digital, three-phase electricity 

meter is a precision device measuring the pow-

er consumption in a three-phase system. The 

meter operates in class B (equivalent to class 

1). The device is equipped with a legible LCD 

and signaling diodes informing about the pres-

ence of voltage of a given phase. ZAMEL LEM-

40 meter is used to monitor power consumption 

of three-phase system in consumer, commer-

cial and industrial applications. The product is 

ideal solution for billing the power consumption 

in garages, workshops, plots of land, tenants of 

facilities or for machinery control. The device 

measures and displays electricity expressed in 

kWh rounded to 2 decimal places (0.01kWh). 

W results are presented on a 6+2 digital display. 

Pulse output of the meter allows connecting 

metering device and presenting the measure-

ment results on the additional display/system. 

The meter can be easily installed in electric 

cabinets because it has compact 4-module de-

sign (4 DIN modules). The device is equipped 

with safety flaps, which can be sealed.

The device should be connected 

to a three-phase network in ac-

cordance with legally binding 

standards. The connection meth-

od is described in this manual. 

Any activities related to instal-

lation, connection, and adjustment should be 

performed  by  qualified  electricians  who  have 

read this user’s manual and familiarised them-

selves with device functions. Removing the 

enclosure voids the warranty and poses a risk 

of electric shock. Before installation, make sure 

that there is no voltage on connection cables. 

To install the device, use a cross-head screw-

driver with a diameter of 3.5 mm. The proper 

operation of the device is affected by how the 

device is transported, stored, and used.  It is not 

advisable to install the device in the following 

cases: lack of any components, damage to or 

deformation of the device. If the device oper-

ates improperly, please contact the manufac-

turer.

NOTE

Do not dispose of this device together with other 

waste! To avoid harmful effects on the environment and 

human health, the worn-out device should be stored 

in designated areas. Electrical waste from households 

may be handed over to the waste collector established 

for this purpose free of change and in any amount, as well as to 

the store when purchasing new equipment.

LCD display

Input terminals 

L1, L2, L3, N

Indication

for pulse counting

Pulse

output 

Output terminals

L1, L2,  L3, N

Voltage

presence indication

Reviews: