ROC364 Instruction Manual
B-8
Local Display Panel
Rev Jun/05
B.3.4.2 Discrete Output Point Display
Each selected Discrete Output returns a display similar to the one in Figure B-9. Press HOLD to stop the
display from automatically scrolling between points. Press SCAN to begin automatically scanning. To
return to the I/O menu display, press MENU. The Discrete Output point display shows the parameters
listed in Table B-5.
DO Tag
PT# A13
OFF EU
0.00
ACC 160461
HOLD
MENU
Figure B-9. Discrete Output Point Display
Table B-5. Discrete Output Point Display Parameters
Parameter Description
DO Tag
10-character identifier Tag for the Discrete Output.
PT#
Module rack letter and Point Number of the Discrete Output as installed in the ROC.
OFF or ON
Status (state) of the Discrete Output. “OFF” indicates that the output is off or that the relay is
open. “ON” indicates that the output is on or that the relay is closed. The Status value can be
changed in the manual mode (Scanning Disabled) to lock an input to either the “OFF” or “ON”
state.
EU
Used only when Discrete Output is configured as a Timed Duration Output (TDO). The output
value is calculated from EU Value using the 0% Count, 100% Count, Low Reading EU, and
High Reading EU parameters.
ACC
Accumulated Value is the number of positive (“0” to “1”) transitions of the Discrete Output.
B.3.4.3 Analog Input Point Display
Figure B-10 shows a typical Analog Input display. Press HOLD to stop the display from automatically
scrolling between points. Press SCAN to begin automatically scanning. To return to the I/O menu
display, press MENU. The Analog Input point display shows the parameters listed in Table B-6.
AI Tag
Units
EU 0.00
ALM 00000011
PT# A2
HOLD
MENU
Figure B-10. Analog Input Point Display