ROC364 Instruction Manual
B-11
Local Display Panel
Rev Jun/05
B.3.4.5 Pulse Input Point Display
The display shown in Figure B-14 is a typical display for each Pulse Input point. Press HOLD to stop
the display from automatically scrolling between points. Press SCAN to begin automatically scanning.
To return to the I/O menu display, press MENU. The Pulse Input point display shows the parameters
listed in Table B-8.
PI Tag
Units
EU 0.00
ALM 00000011
PT# A11
SCAN NEXT PREV MENU
Figure B-14. Pulse Input Point Display
Table B-8. Pulse Input Point Display Parameters
Parameter Description
PI Tag
10-character identifier Tag for the Pulse Input.
Units
10-character unit of measurement identifier for the engineering units (EU) assigned to the
Pulse Input.
EU
If the EU Options flag has been set to Rate (Max Rollover), then the EU / time displays. If
Today’s Total (Max Rollover) was selected, then the EUs accumulated since Contract Hour
display.
PT#
Module rack letter and Point Number of the Pulse Input as installed in the ROC.
ALM
Alarm Code is an 8-bit field. If a bit is set to “1”, the alarm is active. If a bit is set to “0,” the
alarm is cleared.
Figure B-15 shows the alarm code bits and the alarms they represent for a Pulse Input point.
Alarm
Code
0 0
0 0
0 0
0 0
Manual Mode
Low Alarm
Not Used
Low Low Alarm
Not Used
High Alarm
Rate Alarm
High High Alarm
Figure B-15. Pulse Input Alarm Code Bits