3.5 Troubleshooting and Repair
Use troubleshooting and repair to identify and replace faulty modules. Faulty modules must be returned
to your local sales representative for repair or replacement.
If an I/O point does not function correctly, first determine if the problem is with the field device or the
I/O module as follows:
Failure to exercise proper electrostatic discharge precautions (such as wearing a grounded wrist
strap) may reset the processor or damage electronic components, resulting in interrupted
operations.
1.
Isolate the field device from the ROC by disconnecting it at the I/O module terminal block.
2.
Connect the ROC to a computer running ROCLINK configuration software.
3.
Perform the appropriate test procedure described in the following sections.
A module suspected of being faulty should be checked for a short circuit between its input or output
terminals and the ground screw. If a terminal not directly connected to ground reads zero (0) when
measured with an ohmmeter, the module is defective and must be replaced.