A.4 Lightning Protection Module Specifications
Lightning Protection Module Specifications
ELECTRICAL
Series Resistance:
10
Ω
from input to output, each
terminal.
DC Clamping Voltage:
72 to 108 V dc.
100 V/ms Impulse Clamping Voltage:
500 V
maximum.
Clamping Release Voltage:
52 V minimum.
10 KV/µs Impulse
Clamping Voltage:
900 V
maximum.
Surge Life:
Module can withstand 300 surges of 10
to 1000 µs duration at 500 A minimum.
Insulation Resistance:
10,000 M
Ω
minimum.
Capacitance:
1.0 pF maximum @ 1 MHz, each
terminal.
CASE
Material:
ABS polycarbonate thermoplastic.
Dimensions:
17 mm H by 21 mm W by 40 mm D
(0.65 in. H by 0.84 in. W by 1.58 in. D).
Length of Ground wire:
1.2 m (48 in) nominal.
SURGE WITHSTAND
Meets surge requirements IEEEC62.31.
ENVIRONMENTAL
Meets the Environmental specifications of the ROC
in which the module is installed, including
Temperature, Humidity, and Transient Protection.
WEIGHT
34 grams (1.2 ounces).
APPROVALS
Approved by CSA for hazardous locations Class I,
Division 2, Groups A, B, C, and D.