ROC364 Instruction Manual
3-39
Input and Output Modules
Rev Jun/05
3.7.9 Pulse Input Module—Low Level
Pulse Input Module—Low Level Specifications
MODULE RACK TERMINALS
A:
Not used.
B:
Positive Pulse Input.
C:
Negative Pulse Input.
INPUT
Type:
Two-state, voltage-pulse sense.
Active Range:
30 mV minimum to 3 V maximum,
peak-to-peak.
Frequency Response:
0 to 3 kHz, 50% Duty
Cycle.
Impedance:
500 k
Ω
.
POWER REQUIREMENTS
4.9 to 5.1 V dc, 2 mA maximum (supplied by ROC).
INPUT ISOLATION
Isolation:
10 M
Ω
minimum, input or output to case.
Voltage:
4,000 V ac (RMS) minimum, input to
output.
Capacitance:
6 pF typical, input to output.
VIBRATION
20 Gs peak or 0.06 in. double amplitude,
10 to 2,000 Hz, per MIL-STD-202 method 204
condition F.
MECHANICAL SHOCK
1500 Gs 0.5 ms half sine per MIL-STD-202,
method 213, condition F.
CASE
Solvent-resistant thermoplastic polyester, meets
UL94V-0.
Dimensions 15 mm D by 32 H mm by 43 mm (W
0.60 in. D by 1.27 in. H by 1.69 in. W), not
including pins.
WEIGHT
37 g (1.3 oz).
ENVIRONMENTAL
Meets the Environmental specifications of the ROC
in which the module is installed, including
Temperature, Humidity, and Transient Protection.
APPROVALS
Approved by CSA for hazardous locations Class I,
Division 2, Groups A, B, C, and D.