MP120
2.12 GENERAL SYSTEM TIMES
Below are the general system times that can be configured:
•
Entry time
, i.e. the time allowed, by the control unit, to pass between the break-in signalling of a delayed input
and the actuation of the alarm outputs. The time can be chosen from among 0, 5, 10, 15, 20, 30, 40, 50, 60 and
90 seconds.
•
Alarm time
, i.e. the actuation time for the alarm outputs (e.g. the siren actuation time). The time can be chosen
from among 30 seconds, and 1, 2, 3, 4, 5, 6, 7, 8 and 9 minutes.
•
No mains supply
, i.e. the time during which the mains voltage (230 V~) shall not be available before the
respective alarms are actuated. The time can be chosen from among 2 minutes, and 1, 2 and 4 hours.
•
Alarm count
, i.e. the number of times the alarm may be repeated before it is automatically deactivated. The
alarm may be repeated the following times: 0 (no count = unlimited repetitions), 1, 2, 3, 4, 5, 6, 7, 8 and 9 times.
The
Exit time
(i.e. the time allowed, by the control unit, to pass after actuating one or several sectors prior to
considering the alarm signals sent by the detectors of the concerned sectors to be valid) is FIXED and is equal to
the Entry time + 10 seconds.
To modify the general system times, proceed as follows:
1. type in the Installer code (factory setting: 000000), then press
ENTER
twice.
2. The following message will appear on the display:
Press ► until the message below appears:
Then press
ENTER
to confirm.
3. The following message will appear on the display:
Press ▼ until the message below appears:
Then press
ENTER
to confirm.
4. The following message will appear on the display:
where “n” indicates the entry time duration (sec.). To change the time, press
ENTER
and select the new time by
means of button ▼, then confirm the new value by pressing
ENTER
.
5. Press ▼. The following message will appear on the display:
where “nn” indicates the alarm duration (s = seconds, m = minutes). To change the time, press
ENTER
and
select the new time by means of button ▼, then confirm the new value by pressing
ENTER
.
6. Press ▼. The following message will appear on the display:
where “nn” indicates the no mains voltage time (h = hours) elapsing before the outputs for this type of alarm are
actuated. To change the time, press
ENTER
and select the new time by means of button ▼, then confirm the
new value by pressing
ENTER
.
7. Press ▼. The following message will appear on the display:
M A I N F A I L n n
T . A l a r m n n
T . E n t r y n s
T i m e D e l a y / C o u n t .
Z o n e P r o g r a m m i n g
C o n t r . P a n e l P R G
E v e n t M e m o r y