Doc
#
E149701
C-12
C: DNP Mapping
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
30
32
4
Neutral
Current
SINT16
0 to 32767
(10 / 32768)
A
For 1A
model, mul-
tiplier is (2 /
32768) and
values above
2A
secondary
read 32767
30
33
4
PowerFactor,
Phase A
SINT16
-1000 to
+1000
0.001
None
30
34
4
Power Factor,
Phase B
SINT16
-1000 to
+1000
0.001
None
30
35
4
Power Factor,
Phase C
SINT16
-1000 to
+1000
0.001
None
30
36
4
Watts, Phase A
SINT16
-32768 to
+32767
(4500/32768)
W
30
37
4
Watts, Phase B
SINT16
-32768 to
+32767
(4500/32768)
W
30
38
4
Watts, Phase C
SINT16
-32768 to
+32767
(4500/32768)
W
30
39
4
VARs, Phase A
SINT16
-32768 to
+32767
(4500/32768)
VAR
30
40
4
VARS, Phase B
SINT16
-32768 to
+32767
(4500/32768)
VAR
30
41
4
VARs, Phase C
SINT16
-32768 to
+32767
(4500/32768)
VAR
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments