Doc
#
E149701
B-63
B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
same channel. The Return PQ record, which represents the end of a PQ event, will end
the TRUE sequence by having its flag set to FALSE for that channel.
From the event channel byte array perspective, whenever a change occurred within
the present states byte array, it sets its flag for that channel to TRUE. Whenever that
channel reverts back to its previous state, then the event channel flag will be trig-
gered again (set to TRUE) for that channel.
The following is a snippet of the present state and event channel byte arrays:
NOTE:
x = TRUE, empty = FALSE)
Present State (snippet)
Event Channel (snippet)
PQ
Record
Va
Surge
Vb
Surge
Vc
Surge
Timestamp
PQ
Record
Va
Surge
Vb
Surge
Vc
Surge
Timestamp
0
2013/04/01
02:10:13
PM
0
2013/04/01
02:10:13 PM
1
2013/04/01
02:10:14
PM
1
2013/04/01
02:10:14 PM
2
x
2013/04/01
02:10:15
PM
2
x
2013/04/01
02:10:15 PM
3
x x
2013/04/01
02:10:16
PM
3
2013/04/01
02:10:16 PM
4
x
x
2013/04/01
02:10:17
PM
4
x
2013/04/01
02:10:17 PM
5
x
x
2013/04/01
02:10:18
PM
5
2013/04/01
02:10:18 PM
6
x
2013/04/01
02:10:19
PM
6
2013/04/01
02:10:19 PM
7
x
2013/04/01
02:10:20
PM
7
2013/04/01
02:10:20 PM
8
2013/04/01
02:10:21
PM
8
x
2013/04/01
02:10:21 PM
9
2013/04/01
02:10:22
PM
9
2013/04/01
02:10:22 PM
Summary of Contents for Shark 200