The Alarm Log Record uses 16 bytes, 10 bytes of which are available when the log is
retrieved.
The limit # byte is broken into a type and an ID.
3.
Historical Log 1 (2)
: The Historical Log records the values of its assigned regis-
ters at the programmed interval.
NOTE:
See Section B.5.3, Number 1, for details on programming and interpreting the
log.
4.
Historical Log 2 (3)
: Same as Historical Log 1.
5.
Historical Log 3 (4)
: Same as Historical Log 1.
6.
I/O Change Log (5)
: The I/O Change Log records changes in the input and out-
put of Digital I/O Type Option Cards (Relay and Pulse).
I/O Change Log tables:
Card Change Flags:
Byte
0
1
2
3
4
5
6
7
8
9
Value
timestamp
direction
limit#
Value%
Bit
0
1
2
3
4
5
6
7
Value
type
0
0
0
0
Limit ID
Byte
0
1
2
3
4
5
6
-
-
N
Value
timestamp
values . . .
Table 1:
Byte
0
1
2
3
4
5
6
7
8
9
Value
Timestamp
Card 1 Changes
Card 1 States
Card 2 Changes
Card 2 States
Bit
7
6
5
4
3
2
1
0
Value
Out 4
Change
Out 3
Change
Out 2
Change
Out 1
Change
In 4
Change
In 3
Change
In 2
Change
In 1
Change