7: Using the I/O Option Cards
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
7.7: Pulse Output (Solid State Relay Contacts) / Digital Input Card
(P01S)
The Pulse Output/Digital Input card is a combination of pulse outputs via solid state
contacts and dry/wet contact sensing digital inputs. The outputs are electrically
isolated from the inputs and from the main unit.
7.7.1: Specifications
The technical specifications at 25 °C are as follows:
Power consumption:
0.420 W internal
Relay outputs:
Number of outputs:
4
Contact type:
Closing (SPST - NO)
Relay type:
Solid state
Peak switching voltage:
DC ±350 V
Continuous load current:
120 mA
Peak load current:
350 mA for 10 ms
On resistance, max.:
35
Leakage current:
1µA@350 V
Switching Rate max.:
10/s
Isolation:
AC 3750 V system to contacts
Reset/Power down state:
Open contacts
Inputs:
Number of inputs:
4
Sensing type:
Wet or dry contact status detection
Wetting voltage:
DC (12-24) V, internally generated
Input current:
2.5 mA – constant current regulated