Doc
#
E149701
7-8
7: Using the I/O Option Cards
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The general specifications are as follows:
Operating temperature:
(-20 to +70) °C
Storage temperature:
(-40 to +80) °C
Relative air humidity:
Maximum 95%, non-condensing
EMC - Immunity interference:
EN61000-4-2
Weight:
1.6 oz
Dimensions (inch) W x H x L:
0.72 x 2.68 x 3.26
External connection:
AWG 12-26/(0.129 - 3.31) mm
2
5 pin, 0.200” pluggable terminal block
7.5.2: Default Configuration:
The Shark® 200 meter automatically recognizes the installed Option card during
power up. If you have not programmed a configuration for the card, the unit defaults
to the following outputs:
Channel 1
+Watts, +1800 Watts => 20 mA
-Watts, -1800 Watts => 4 mA
0 Watts => 12 mA
Channel 2
+VARs, +1800 VARs => 20 mA
- VARs, -1800 VARs => 4 mA
0 VARs => 12 mA
Channel 3
Phase A Voltage WYE, 300 Volts => 20 mA
0 Volts => 4 mA
Phase A Voltage Delta, 600 Volts => 20 mA
Channel 4
Phase A Current, 10 A => 20 mA
0 Phase A Current, 0 A => 4 mA
Summary of Contents for Shark 200
Page 1: ...V 1 24 March 15 2018 ...