6: Using the Shark® 200 Meter
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Figure 6.5: Using the Watt Hour Test Pulse
Table 6.1: Infrared & KYZ Pulse Constants for Accuracy Testing - Kh Watt hour per pulse
NOTES:
• Minimum pulse width is 90 milliseconds.
• Refer to Chapter 2, Section 2.2, for Wh Pulse specifications.
• Typical standards are: Radian Research RD20 & RD21 or a Watt hour Engineering
Company Three Phase Automated Test System.
NOTE:
Watt hour Standards offer pulse inputs that take in the CPU's test pulses. The
accuracy is computed by ratio-metrically comparing the period of the meter's pulse to
the period of the Standard's internal pulse. You must program the test pulse value
(Kh) into the Standard for the results to be accurate.