B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Item Descriptor List:
Registers:
0x798E - 0x79C8
Size:
1 byte per item, 117 bytes (59 registers)
While the Register List describes what to log, the Item Descriptor List describes how
to interpret that information. Each descriptor describes a group of register items, and
what they mean.
Each descriptor is composed of 2 parts:
• Type: The data type of this descriptor, such as signed integer, IEEE floating point,
etc. This is the high nibble of the descriptor byte, with a value in the range of 0-14.
If this value is 0xFF, the descriptor should be ignored.
0
ASCII: An ASCII string, or byte array
1
Bitmap: A collection of bit flags
2
Signed Integer: A 2's Complement integer
3
Float: An IEEE floating point
4
Energy: Special Signed Integer, where the value
is adjusted by the energy settings in the meter's
Programmable Settings.
5
Unsigned Integer
6
Signed Integer 0.1 scale: Special Signed Integer,
where the value is divided by 10 to give a 0.1
scale.
7-14
Unused
15
Disabled: used as end list marker.
• Size: The size in bytes of the item described. This number is used to determine the
pairing of descriptors with register items.
For example: If the first descriptor is 4 bytes, and the second descriptor is 2 bytes,
then the first 2 register items belong to the 1st descriptor, and the 3rd register item
belongs to the 2nd descriptor.