B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• Valid in the range of -200.0% to +200.0%.
• Stored as an integer with 0.1 resolution. (Multiply % by 10 to get the integer,
divide integer by 10 to get %. For example, 104.1% = 1041.)
• Below Setpoint: The percent of the Full Scale below which the value for this limit
will be considered "out."
• Valid in the range of -200.0% to +200.0%.
• Stored as an integer with 0.1 resolution. (Multiply % by 10 to get the integer,
divide integer by 10 to get %. For example, 93.5% = 935.)
• Below Hysteresis: The percent of the Full Scale above which the limit will return
"into" limit, if it is out. If this value is below the Below Setpoint, this Below limit will
be disabled.
• Valid in the range of -200.0% to +200.0%.
• Stored as an integer with 0.1 resolution. (Multiply % by 10 to get the integer,
divide integer by 10 to get %. For example, 94.9% = 949.)
NOTES
:
• The Full Scale is the "nominal" value for each of the different types of readings. To
compute the Full Scale, use the following formulas:
Current
[CT Numerator] x [CT Multiplier]
Voltage
[PT Numerator] x [PT Multiplier]
Power 3-Phase (WYE)
[CT Numerator] x [CT Multiplier] x [PT Numera-
tor] x [PT Multiplier] x 3
Power 3-Phase (Delta)
[CT Numerator] x [CT Multiplier] x [PT Numera-
tor] x [PT Multiplier] x 3 x sqrt(3)
Power Single Phase (WYE)
[CT Numerator] x [CT Multiplier] x [PT Numera-
tor] x [PT Multiplier]
Power Single Phase (Delta)
[CT Numerator] x [CT Multiplier] x [PT Numera-
tor] x [PT Multiplier] x sqrt(3)