Doc
#
E149701
C-4
C: DNP Mapping
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
C.5: Error Reply
In the case of an unsupported function, or any other recognizable error, an error reply
is generated from the Shark® 200 meter to the Primary station (the requester). The
Internal Indicator field will report the type of error: unsupported function or bad
parameter.
The broadcast acknowledge and restart bit are also signaled in the Internal Indicator
field, but they do not indicate an error condition.
C.6: Object Specifics
• Object 1 - Binary Input Status with Flags - These data points are mapped to the
Digital Inputs on any Digital Relay Cards (RO1S) installed in the Shark® meter.
They are only available if at least one Digital Relay Card is installed in the meter.
The inputs on a card in Slot 1 are mapped to Points 0 and 1. The inputs on a card in
Slot 2 are mapped to Points 2 and 3. If there is no card installed in a slot, those
points will return a status with the “Offline” bit set.
• Object 10 - Binary Output States - These data points are mapped to the Digital
Relays on any Digital Relay Cards (RO1S) installed in the Shark® meter. Data
Points 3 through 6 are only available if there is at least one Digital Relay Card
(RO1S) installed in the meter. The relays on a card in Slot 1 are mapped to Points 3
and 4. The relays on a card in Slot 2 are mapped to Points 5 and 6. If there is no
card installed in a slot, those points will return a status with the "Offline" bit set.
• Object 12 - Control Relay Outputs - Points 0-2 reference internal controls. Points 3-
6 are mapped to the Digital Relays on any Digital Relay Card (RO1S) installed in the
Shark® meter. Control requests to relays not installed will return an unknown
object response. See C.4: Application Layer on page C-2 for specific control mecha-
nisms. Any relays that have been Assigned to a limit cannot be controlled via this
command: the response status code will be 10 - Automation Inhibit, and no action
will be taken.
• Object 20 - Binary Counters (Primary Readings) - Points 0-4 are mapped to Primary
Energy readings, Points 5-8 are mapped to the Digital Inputs on any Digital Relay
Card (RO1S) installed in the Shark® meter. If the digital inputs are set up as accu-
mulators they can be read via this request; if they are not set up as accumulators
the response will always be zero.
Summary of Contents for Shark 200
Page 1: ...V 1 24 March 15 2018 ...