Object 30 - Analog Inputs (Primary Readings)
Read with Object 30, Var 4, and Qualifiers 0, 1, 2, or 6. (Included in Class 0
responses.)
NOTE:
Multipliers for Volts, Amps, and Power points are per user setup options.
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
30
0
4
Meter Health
SINT16
0 or 1
N/A
None
0 = OK
30
1
4
Volts A-N
SINT16
0 to 32767
1, 10, or 100
V
Point value
= Actual
Volts/divisor
30
2
4
Volts B-N
SINT16
0 to 32767
1, 10, or 100
V
30
3
4
Volts C-N
SINT16
0 to 32767
1, 10, or 100
V
30
4
4
Volts A-B
SINT16
0 to 32767
1, 10, or 100
V
30
5
4
Volts B-C
SINT16
0 to 32767
1, 10, or 100
V
30
6
4
Volts C-A
SINT16
0 to 32767
1, 10, or 100
V
30
7
4
Amps A
SINT16
0 to 32767
1 or 10
A
Point value
= Actual
Amps/divisor
30
8
4
Amps B
SINT16
0 to 32767
1 or 10
A
30
9
4
Amps C
SINT16
0 to 32767
1 or 10
A
30
10
4
Watts, 3-Ph
total
SINT16
-32768 to
+32767
1, 10, 100 or
1000
W
Point value
= Actual
kWatts/divi-
sor
30
11
4
VARs, 3-Ph
total
SINT16
-32768 to
+32767
1, 10, 100 or
1000
VAR
30
12
4
VAs, 3-Ph total
SINT16
0 to +32767
1, 10, 100 or
1000
VA
30
13
4
Power Factor,
3-Ph total
SINT16
-1000 to
+1000
0.001
None
30
14
4
Frequency
SINT16
0 to 9999
0.01
Hz
30
15
4
Positive Watts,
3-Ph,
Maximum Avg
Demand
SINT16
-32768 to
+32767
1, 10, 100, or
1000
W