7: Using the I/O Option Cards
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Minimum input voltage:
0 V (input shorted to common)
Maximum input voltage:
DC 150 V (diode protected against polarity
reversal)
Filtering:
De-bouncing with 50ms delay time
Detection scan rate:
100 ms
Isolation:
AC 2500 V system to inputs
The general specifications are as follows:
Operating Temperature:
(-20 to +70) °C
Storage Temperature:
(-40 to +80) °C
Relative air humidity:
Maximum 95%, non-condensing
EMC - Immunity Interference:
EN61000-4-2
Weight:
1.3 oz
Dimensions (inch) W x H x L:
0.72 x 2.68 x 3.26
External Connection:
AWG 12-26/(0.129 - 3.31) mm
2
13 pin, 3.5 mm pluggable terminal block
7.7.2: Default Configuration:
The Shark® 200 meter automatically recognizes the installed Option card during
power up. If you have not programmed a configuration for the card, the unit defaults
to the following outputs:
Status Inputs
Defaulted to Status Detect
Pulse Outputs
Defaulted to Energy Pulses
Pulse Channel 1
1.8 +Watt-hours per pulse
Pulse Channel 2
1.8 -Watt-hours per pulse