Doc
#
E149701
C-15
C: DNP Mapping
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Object 80 - Internal Indicator
C.8: DNP Message Layouts
Legend
All numbers are in hexadecimal base. In addition the following symbols are used.
30
36
4
Watts, Phase A
SINT16
-32768 to
+32767
(4500/32768)
W
30
37
4
Watts, Phase B
SINT16
-32768 to
+32767
(4500/32768)
W
30
38
4
Watts, Phase C
SINT16
-32768 to
+32767
(4500/32768)
W
30
39
4
VARs, Phase A
SINT16
-32768 to
+32767
(4500/32768)
VAR
30
40
4
VARS, Phase B
SINT16
-32768 to
+32767
(4500/32768)
VAR
30
41
4
VARs, Phase C
SINT16
-32768 to
+32767
(4500/32768)
VAR
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
80
7
1
Device Restart Bit
N/A
N/A
N/A
none
Clear via
Function 2
(Write),
Qualifier
Code 0.
dst
16 bit frame destination address
src
16 bit frame source address
crc
DNP Cyclic redundant checksum (polynomial
x
16
+x
13
+x
12
+x
11
+x
10
+x
7
+x
6
+x
5
+x
2
+1)
x
transport layer data sequence number
y
application layer data sequence number
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
Summary of Contents for Shark 200