Doc
#
E149701
B-38
B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
I/O Change Log Record
:
I/O Change Log tables:
Card Change Flags:
Card Current States:
Size
: 10 bytes (16 bytes)
Data
: The states of the relay and digital inputs at the time of capture for both Option
cards 1 and 2. If the option card does not support I/O Change Records (no card or not
a Digital Option Card), the value will be 0.
NOTES
:
• An I/O Change log record will be taken for each Relay and Digital Input that has
been configured in the Programmable Settings to record when its state changes.
• When any one configured Relay or Digital Input changes, the values of all Relays
and Digital Inputs are recorded, even if they are not so configured.
Byte
0
1
2
3
4
5
6
7
8
9
Value
Timestamp
Card 1 Changes
Card 1 States
Card 2 Changes
Card 2 States
Bit
7
6
5
4
3
2
1
0
Value
Out 4
Change
Out 3
Change
Out 2
Change
Out 1
Change
In 4
Change
In 3
Change
In 2
Change
In 1
Change
Bit
7
6
5
4
3
2
1
0
Value
Out 4
State
Out 3
State
Out 2
State
Out 1
State
In 4
State
In 3
State
In 2
State
In 1
State
Summary of Contents for Shark 200