Doc
#
E149701
B-56
B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
else
triggered_str = trigger "Vcn=Sag";
break;
case 15
:
triggered_str = trigger "Manual Trigger";
break;
}
}
}
The trigger cycle tag value from the waveform capture header provides the specific
cycle within the waveform capture on which the trigger condition occurred.
To give an example of what the trigger cycle tag provides, the following is a snippet
from a CSV generated output of the raw sample values (non-primary values) from a
waveform capture. The index at which the samples are located within the CSV file is
specified in the first column. With a trigger cycle tag of 512 and the following table:
SAMPLES
INDEX
VOLTS
AN
CURRENT
IA
VOLTS
BN
CURRENT
IB
VOLTS
CN
CURRENT
IC
27
0
0
0
0
0
0
28
6768
6792
5840
6800
5784
6880
29
6480
6736
5872
6816
5792
6936
30
6280
6776
5864
6872
5816
6960
31
6008
6784
5872
6792
5768
6904
32
5728
6736
5864
6864
5856
6960
536
7408
6712
5832
6808
5800
6984
537
7248
6776
5880
6848
5848
6984
538
7000
6776
5896
6864
5848
6928
539
6712
6752
5864
6808
5800
6976
Summary of Contents for Shark 200