SEFELEC1500M Instructions
117
V1.06
12.4. DEFINITION OF THE INPUT-OUTPUT SIGNALS
COMIN (C6-5)
Electric common for the input signals.
COMOUT (C7-4)
Electric common for the output signals.
CTRLIN (Input C6-6)
Request to take control of the measuring instrument by the PLC.
MES_DCH (Input C7-2)
Switch to measurement or discharge.
At logic high: Measurement.
At logic low: Discharge.
TYPE (Input C7-1)
This input corresponds to the old selection of the XS series measurement function, with
the Sefelec series:
-
At logic low : shifts 256-position memory numbers (256-512)
-
Logically high : does not shift memory numbers. (0-256)
N0, N1, N2, N3 (Input C6-7,8,9,10)
N4, N5, N6, N7 (Input C8-1,2,3,4)
Binary coding making it possible to select a parameter memory number and an associated
file.
N7
N6
N5
N4
N3
N2
N1
N0
Memory
Filename
0
0
0
0
0
0
0
0
0
Nom1
0
0
0
0
0
0
0
1
1
Nom2
0
0
0
0
0
0
1
0
2
Nom3
0
0
0
0
0
0
1
1
3
Nom4
0
0
0
0
0
1
0
0
4
Nom5
0
0
0
0
0
1
0
1
5
…
0
0
0
0
0
1
1
0
6
….
0
0
0
0
0
1
1
1
7
….
0
0
0
0
0
1
0
0
8
….
0
0
0
0
1
0
0
1
9
….
….
….
….
….
….
….
….
….
….
….
1
1
1
1
1
1
1
1
255
Nom256
The file names only correspond to Sequence files. To run a measurement function only, put only
one call line of the desired function in the Sequence.