Shutdown
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
78
Figure 55 shows a graph of a shutdown initiated by the “Low battery power” message.
Figure 55. Shutdown Initiated by Low Battery Power
Power Restoration Before End of Shutdown Duration
If power is restored before the end of the Shutdown Duration, the UPS is shut off after the Shutdown Duration
for a time equal to the forced reboot delay (10 seconds). Figure 56 shows a graph of a power restoration before
the end of the Shutdown Duration.
Figure 56. Power Restoration Before End of Shutdown Duration