Configuring the Card
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
49
Environment Status
The Environment Status page displays the status of the optional EMP (see Figure 38).
Figure 38. Environment Status Page
Temperature and humidity measurements are displayed in a graduated bar (see Figure 39).
Figure 39. Graduated Bar (Humidity Bar Shown)
Status parameters:
l
Cursor:
Indicates the current reading.
l
Red zones
: The red zones to the left and right represent the low and high thresholds that can be set on the
Environment Settings page.
If notification is turned on, an alarm is generated when the measured value enters one of these zones.
l
Reset Min/Max:
For temperature or humidity, displays the time-stamped minimum and maximum since the
previous reset.
l
Calibrate:
The EMP is factory-calibrated, but you can apply an offset to adjust the measurement.
l
Input #1
and
Input #2:
The position of the two contacts acquired by the EMP.
The last status change of each contact is time-stamped.
The Internet browser updates this page every 10 seconds.
Low Threshold
High Threshold
Current Reading