Using the Telnet/SSH/CLI Interface
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
61
Enviroment Commands
Use environment commands to define settings for environmental sensors (see Table 21).
Table 21. Environment Commands
getEnv
To read an environment setting
Syntax
getEnv [option1]
Options
Name
Example
#> getEnv Name
setEnv
To modify an environment setting
Syntax
setEnv [option1]
Options
Name = “xx..xx”
Example
#> setEnv Name=”sensor”
getTemp
To read a temperature setting
Syntax
getTemp [option1] [option2] ...
Options
Unit
HighThreshold
LowThreshold
Hysteresis
Offset
HighNotify
LowNotify
HighShutdown
LowShutdown
Example
#> getTemp Unit
setTemp
To modify a temperature setting
Syntax
setTemp [option1] [option2] ...
Options
Unit = C|K
HighThreshold = xx
LowThreshold = xx
Hysteresis = xx (0..5)
Offset = xx (-5..5)
HighNotify = 0|1 (0=No, 1=Yes)
LowNotify = 0|1 (0=No, 1=Yes)
HighShutdown = 0|1 (0=No, 1=Yes)(NOTE 1)
LowShutdown = 0|1 (0=No, 1=Yes) (NOTE 1)
Example
#> setTemp Unit=C
Comments
(NOTE 1) :
W
riting enabled only if the notification is enabled
getHum
To read a humidity setting
Syntax
getHum [option1] [option2] ...
Options
HighThreshold
LowThreshold
Hysteresis
Offset
HighNotify
LowNotify
HighShutdown
LowShutdown