Configuring the Card
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
27
UPS Control
Select
UPS Control
from the menu bar to open the UPS Control page (see Figure 21).
Figure 21. UPS Control Page
The UPS Control page enables triggering of startup and shutdown sequences for the UPS main output and load
segments.
The status of each output displays by a icon associated with the Off label (red icon) or On label (green icon).
The shutdown sequences allow time for the registered servers to shut down without losing data
(see “Shutdown Parameters” on page 29).
The Master has priority over the load segments. Shutdown of the Master causes the load segments to shut
down. Load segments can be started only if the Master is on.
The list in the Control column displays the following commands, which are initialized by clicking
Execute
. These
commands include:
l
Safe power down:
Immediately launches a sequence to switch off output power. The command shuts down
the supplied systems while the shutdown sequence runs, then switches off the output.
l
Safe power down & reboot:
Immediately launches a sequence to switch off and then restore output power. It
shuts down the powered systems during the shutdown sequence, and then switches off the output. Finally,
it launches the restart sequence at the end of the time delay specified in the
Toggle duration
parameter. The
output status is updated.
l
Immediate On:
Immediately launches a sequence to switch on output power. The output is re-powered. This
command can start the system if the system’s basic input/output system (BIOS) settings allow a reboot.
l
Delayed, safe power down:
This is the same switch off sequence as for the
Safe power down
command, but
postponed by the number of seconds programmed in the
Off Delay
parameter.
NOTE
The UPS Control page requires that you are logged in. If you are not logged in when
you select UPS Control, the Login window opens (see “Logging In” on page 14).