MIB Objects
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
64
xupsOutputLoad
Percent
{4.1.0}
xupsOutputFrequency
0.1 Hertz
{4.2.0}
xupsOutputNumPhases
Integer
{4.3.0}
xupsOutputTable
—
{4.4.0}
xupsOutputPhase
Integer
{4.4.1.1.x}
xupsOutputVoltage
RMS Volts
{4.4.1.2.x}
xupsOutputCurrent
RMS Amps
{4.4.1.3.x}
xupsOutput
W
atts
W
atts
{4.4.1.4.x}
xupsOutputSource
Integer
{4.5.0}
xupsBypassFrequency
0.1 Hertz
{5.1.0}
xupsBypassNumPhases
Integer
{5.2.0}
xupsBypassTable
—
{5.3.0}
xupsBypassPhase
Integer
{5.3.1.1.x}
xupsBypassVoltage
RMS Volts
{5.3.1.2.x}
xupsEnvAmbientTemp
Degrees C
{6.1.0}
xupsEnvAmbientLowerLimit
Degrees C
{6.2.0}
xupsEnvAmbientUpperLimit
Degrees C
{6.3.0}
xupsEnvAmbientHumidity
Percent
{6.4.0}
xupsEnvRemoteTemp
Degrees C
{6.5.0}
xupsEnvRemoteHumidity
Percent
{6.6.0}
xupsEnvNumContacts
Integer
{6.7.0}
xupsContactSenseTable
table
{6.8.0}
xupsContactIndex
Integer
{6.8.1.1.x}
xupsContactType
Integer
{6.8.1.2.x}
xupsContactState
Integer
{6.8.1.3.x}
xupsContactDescr
String
{6.8.1.4.x}
xupsEnvRemoteTempLowerLimit
Degrees C
{6.9.0}
xupsEnvRemoteTempUpperLimit
Degrees C
{6.10.0}
xupsEnvRemoteHumidityLowerLimit
Percent
{6.11.0}
xupsEnvRemoteHumidityUpperLimit
Percent
{6.12.0}
xupsAlarmTable
table
{7.2.0}
xupsAlarmID
—
{7.2.1.1.x}
xupsAlarmDescr
—
{7.2.1.2.x}
xupsAlarmTime
—
{7.2.1.3.x}
xupsOnBattery
—
{7.3.0}
xupsLowBattery
—
{7.4.0}
xupsUtilityPowerRestored
—
{7.5.0}
xupsReturnFromLowBattery
—
{7.6.0}
upsOutputOverload
—
{7.7.0}
xupsInternalFailure
—
{7.8.0}
xupsBatteryDischarged
—
{7.9.0}
xupsInverterFailure
—
{7.10.0}
Table 22. PowerMIB Objects (Continued)
MIB Object
SNMP Format
Add.path