Chapter 16 PLC Function Applications
│
CP2000
16-29
Functions of auxiliary relays
Like an output relay Y, an auxiliary relay M has an output coil and contacts a and b, and the
number of times they can be used in a program is unrestricted. Users can use an auxiliary relay M to
configure the control circuit, but cannot use it to directly drive an external load. Auxiliary relays have
the following two types of characteristics:
Ordinary auxiliary relays: Ordinary auxiliary relays will all revert to the Off state if a power outage
occurs while the PLC is running, and will remain in the Off state if power is again
turned down.
Special purpose auxiliary relays: Each special purpose auxiliary relay has its own specific use. Do not
use any undefined special purpose auxiliary relays.
Timer functions
Timers take 100 ms as their timing units. When the timing method is an upper time limit, when
the current timer value = set value, power will be sent to the output coil. Timer setting values consist
of decimal K values, and the data register D can also serve as a setting value.
Actual timer setting time = timing units * set value
Counter features
Item
16-bit counter
Type
General Type
CT Direction:
Score:
Setting
0–32,767
Designation of set value Constant K or data register D
Change in current value When the count reaches the set value, there is no longer a count
Output contact
When the count reaches the set value, the contact comes On and stays On
Reset
The current value reverts to 0 when an RST command is executed, and the
contact reverts to Off
Contact actuation
All are actuated after the end of scanning
Counter functions
When a counter's counting pulse input signal goes OFF→ON, if the counter's current value is
equal to the set value, the output coil will become ON. The setting value will be a decimal K values,
and the data register D can also serve as a setting value.
16-bit counter C0
–
C79:
16-bit counter setting range: K0
–
K32,767. (when K0 and K1 are identical, the output contact
will immediately be ON during the first count.)
The current counter value will be cleared from an ordinary counter when power is shut off to the
PLC.
If the MOV command or WPLSoft is used to transmit a value greater than the set value to the
C0 current value register, when the next X1 goes from OFF→ON, the C0 counter contact will
change to On, and the current value will change to the set value.
A counter's setting value may be directly set using a constant K or indirectly set using the value
in register D (not including special data registers D1000
–
D1199 or D2000
–
D2799).
If the set value employs a constant K, it may only be a positive number; the set value may be
either a positive or a negative number if the value in data register D is used. The current
counter value will change from 32,767 to -32,768 as the count continues to accumulate.
Summary of Contents for CP2000 Series
Page 3: ......
Page 12: ...Chapter 1 Introduction CP2000 1 3 1 2 Model Name 1 3 Serial Number...
Page 35: ...Chapter 1 Introduction CP2000 1 26 Digital Keypad KPC CC01 Figure 1 32...
Page 42: ...Chapter 3 Unpacking CP2000 3 1 Chapter 3 Unpacking 3 1 Unpacking 3 2 The Lifting Hook...
Page 72: ...Chapter 4 Wiring CP2000 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Page 77: ...Chapter 4 Wiring CP2000 4 6 Figure 4 5...
Page 79: ...Chapter 4 Wiring CP2000 4 8 This page intentionally left bank...
Page 109: ...Chapter 6 Control Terminals CP2000 6 12 This page intentionally left blank...
Page 172: ...Chapter 7 Optional Accessories CP2000 7 63 EMC filter model name EMF018A43A Figure 7 46...
Page 174: ...Chapter 7 Optional Accessories CP2000 7 65 EMC filter model name KMF370A KMF3100A Figure 7 48...
Page 175: ...Chapter 7 Optional Accessories CP2000 7 66 EMC filter model name B84143D0150R127 Figure 7 49...
Page 176: ...Chapter 7 Optional Accessories CP2000 7 67 EMC filter model name B84143D0200R127 Figure 7 50...
Page 182: ...Chapter 7 Optional Accessories CP2000 7 73 Wall Mounting Embedded Mounting...
Page 197: ...Chapter 7 Optional Accessories CP2000 7 88 6 Installation complete...
Page 237: ...Chapter 7 Optional Accessories CP2000 7 128 This page intentionally left blank...
Page 265: ...Chapter 8 Option Cards CP2000 8 28 This page intentionally left blank...
Page 277: ...Chapter 09 Specifications CP2000 9 12 575V 690V Figure 9 3 Altitude Derating Curve Figure 9 4...
Page 281: ...Chapter 09 Specifications CP2000 9 16 9 8 Efficiency Curve Figure 9 11 Figure 9 12...
Page 317: ...Chapter 10 Digital Keypad CP2000 10 36 This page intentionally left blank...
Page 361: ...Chapter 11 Summary of Parameter Settings CP2000 11 44 This page intentionally left blank...
Page 416: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 3 3 4 5...
Page 417: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 4 6 7 8...
Page 418: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 5 9 10 11...
Page 419: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 6 12 13 14...
Page 420: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 7 15 16 17...
Page 421: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 8 18 19 20...
Page 422: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 9 21 22 23...
Page 423: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 10 24 25 26...
Page 424: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 11 27 28 29...
Page 425: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 12 30 31 32...
Page 426: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 13 33 34 35...
Page 427: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 14 36 37 38...
Page 836: ...Chapter 16 PLC Function Applications CP2000 16 153...
Page 838: ...Chapter 16 PLC Function Applications CP2000 16 155...
Page 841: ...Chapter 16 PLC Function Applications CP2000 16 158 This page intentionally left blank...
Page 857: ...Chapter 17 Introduction to BACnet CP2000 17 16 This page intentionally left blank...