Chapter 12 Description of Parameter Settings
CP2000
12.1-10-2
estimator measure the rotor right position and speed when running at the switch point
frequency.
If the switch point is too high, the active area of I/F is too wide, which generates more current
and cannot save energy. If the current value for Pr.10-31 is too high, the high switch point
makes the drive continue to output with the setting value for Pr.10-31).
I/F Mode, Id Current Low-Pass Filter Time
Default: 0.2
Settings 0.0–6.0 sec.
Sets the filter time for Pr.10-31. Smoothly increases the magnetic field to the current command
setting value under the I/F mode.
If you want to slowly increase the size of Id, increase the filter time to avoid a Step phenomenon
occurs when starting current output. When decrease the filter time (minimum value is 0), the
current rises faster, then a Step phenomenon occurs.
Initial Angle Detection Pulse Value
Default: 1.0
Settings 0.0–3.0 times of motor rated current
This parameter is valid only when setting of Pr.10-53=2 or 3.
The parameter influences the value of the pulse during the angle detection. The larger the pulse,
the higher the accuracy of rotator’s position. A larger pulse might cause oc.
Increase the parameter when the running direction and the command are opposite during
start-up. If oc occurs at start-up, then decrease the parameter.
Refer to Section 12-2 Adjustment & Application for detailed motor adjustment procedure.
Zero Voltage Time while Start-up
Default: 0.000
Settings
0.000–60.000 sec.
This parameter is valid only when the setting of Pr. 07-12 (Speed Tracking during Start-up) = 0.
When the motor is in static status at the start-up, this increases the accuracy when estimating
angles. In order to put the motor in static status, set the three-phase drive output to 0 V to the
motor. The Pr.10-49 setting time is the length of time when three-phase output at 0 V.
It is possible that even when you apply this parameter, the motor cannot go into the static state
because of inertia or some external force. If the motor does not go into the static status in 0.2
seconds, increase the setting value appropriately.
If Pr.10-49 is too high, the start-up time is longer. If it is too low, the braking performance is
weak.
Injection Frequency
Default: 500
Settings 0–1200 Hz
This parameter is a high frequency injection command in PM SVC control mode and usually you
do not need to adjust it. If a motor’s rated frequency (for example, 400 Hz) is too close to the
frequency setting for this parameter (that is, the default is 500 Hz), it affects the accuracy of the
Summary of Contents for CP2000 Series
Page 3: ......
Page 12: ...Chapter 1 Introduction CP2000 1 3 1 2 Model Name 1 3 Serial Number...
Page 35: ...Chapter 1 Introduction CP2000 1 26 Digital Keypad KPC CC01 Figure 1 32...
Page 42: ...Chapter 3 Unpacking CP2000 3 1 Chapter 3 Unpacking 3 1 Unpacking 3 2 The Lifting Hook...
Page 72: ...Chapter 4 Wiring CP2000 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Page 77: ...Chapter 4 Wiring CP2000 4 6 Figure 4 5...
Page 79: ...Chapter 4 Wiring CP2000 4 8 This page intentionally left bank...
Page 109: ...Chapter 6 Control Terminals CP2000 6 12 This page intentionally left blank...
Page 172: ...Chapter 7 Optional Accessories CP2000 7 63 EMC filter model name EMF018A43A Figure 7 46...
Page 174: ...Chapter 7 Optional Accessories CP2000 7 65 EMC filter model name KMF370A KMF3100A Figure 7 48...
Page 175: ...Chapter 7 Optional Accessories CP2000 7 66 EMC filter model name B84143D0150R127 Figure 7 49...
Page 176: ...Chapter 7 Optional Accessories CP2000 7 67 EMC filter model name B84143D0200R127 Figure 7 50...
Page 182: ...Chapter 7 Optional Accessories CP2000 7 73 Wall Mounting Embedded Mounting...
Page 197: ...Chapter 7 Optional Accessories CP2000 7 88 6 Installation complete...
Page 237: ...Chapter 7 Optional Accessories CP2000 7 128 This page intentionally left blank...
Page 265: ...Chapter 8 Option Cards CP2000 8 28 This page intentionally left blank...
Page 277: ...Chapter 09 Specifications CP2000 9 12 575V 690V Figure 9 3 Altitude Derating Curve Figure 9 4...
Page 281: ...Chapter 09 Specifications CP2000 9 16 9 8 Efficiency Curve Figure 9 11 Figure 9 12...
Page 317: ...Chapter 10 Digital Keypad CP2000 10 36 This page intentionally left blank...
Page 361: ...Chapter 11 Summary of Parameter Settings CP2000 11 44 This page intentionally left blank...
Page 416: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 3 3 4 5...
Page 417: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 4 6 7 8...
Page 418: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 5 9 10 11...
Page 419: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 6 12 13 14...
Page 420: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 7 15 16 17...
Page 421: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 8 18 19 20...
Page 422: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 9 21 22 23...
Page 423: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 10 24 25 26...
Page 424: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 11 27 28 29...
Page 425: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 12 30 31 32...
Page 426: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 13 33 34 35...
Page 427: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 14 36 37 38...
Page 836: ...Chapter 16 PLC Function Applications CP2000 16 153...
Page 838: ...Chapter 16 PLC Function Applications CP2000 16 155...
Page 841: ...Chapter 16 PLC Function Applications CP2000 16 158 This page intentionally left blank...
Page 857: ...Chapter 17 Introduction to BACnet CP2000 17 16 This page intentionally left blank...