Chapter 14 Fault Codes and Descriptions
CP2000
14-20
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
24_2
Motor overheating
(oH3) PT100
Motor overheating (PT100) (Pr.03-00–Pr.03-02=11
PT100). When PT100 input > Pr.06-57 (default = 7V),
the fault treatment acts according to Pr.06-29.
Action and Reset
Action level
PT100 input value > Pr.06-57 setting (default = 7V)
Action time
Immediately act
Fault treatment parameter
Pr.06-29
0: Warn and keep operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Reset method
When Pr.06-29=0 and the temperature < Pr.06-56, oH3 is automatically cleared.
When Pr.06-29=1 or 2, oH3 is a “Fault”. You must reset manually.
Reset condition
Immediately reset
Record
When Pr.06-29=1 or 2, oH3 is a “Fault”, and the fault is recorded.
Cause
Corrective Actions
Motor shaft lock
Remove the shaft lock.
The load is too large
Reduce the load.
Increase the motor capacity.
Ambient temperature is too high
Change the installed place If there are heating devices in the surroundings.
Install/ add cooling fan or air conditioner to lower the ambient temperature.
Motor cooling system error
Check the cooling system to make it work normally.
Motor fan error
Replace the fan.
Operate at low-speed too long
Decrease low-speed operation time.
Replace the motor with a dedicated to VFD model.
Increase the motor capacity.
Accel./Decel. time and working
cycle are too short
Increase the setting values for Pr.01-12–Pr.01-19 (accel./decel. time)
V/F voltage is too high
Adjust settings for Pr.01-01–01-08 (V/F curve), especially the setting value for
the mid-point voltage (if the mid-point voltage is set too low, the load capacity
decreases at low speed).
Check if the motor rated current
matches that on the motor
nameplate.
Reset to the correct motor rated current.
Check if the PT100 is properly set
and wired.
Check connection of PT100 thermistor.
Check if the setting for stall
prevention is correct.
Set the stall prevention to the proper value.
Unbalanced three-phase
impedance of the motor
Replace the motor.
Harmonics are too high
Use remedies to reduce harmonics.
Summary of Contents for CP2000 Series
Page 3: ......
Page 12: ...Chapter 1 Introduction CP2000 1 3 1 2 Model Name 1 3 Serial Number...
Page 35: ...Chapter 1 Introduction CP2000 1 26 Digital Keypad KPC CC01 Figure 1 32...
Page 42: ...Chapter 3 Unpacking CP2000 3 1 Chapter 3 Unpacking 3 1 Unpacking 3 2 The Lifting Hook...
Page 72: ...Chapter 4 Wiring CP2000 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Page 77: ...Chapter 4 Wiring CP2000 4 6 Figure 4 5...
Page 79: ...Chapter 4 Wiring CP2000 4 8 This page intentionally left bank...
Page 109: ...Chapter 6 Control Terminals CP2000 6 12 This page intentionally left blank...
Page 172: ...Chapter 7 Optional Accessories CP2000 7 63 EMC filter model name EMF018A43A Figure 7 46...
Page 174: ...Chapter 7 Optional Accessories CP2000 7 65 EMC filter model name KMF370A KMF3100A Figure 7 48...
Page 175: ...Chapter 7 Optional Accessories CP2000 7 66 EMC filter model name B84143D0150R127 Figure 7 49...
Page 176: ...Chapter 7 Optional Accessories CP2000 7 67 EMC filter model name B84143D0200R127 Figure 7 50...
Page 182: ...Chapter 7 Optional Accessories CP2000 7 73 Wall Mounting Embedded Mounting...
Page 197: ...Chapter 7 Optional Accessories CP2000 7 88 6 Installation complete...
Page 237: ...Chapter 7 Optional Accessories CP2000 7 128 This page intentionally left blank...
Page 265: ...Chapter 8 Option Cards CP2000 8 28 This page intentionally left blank...
Page 277: ...Chapter 09 Specifications CP2000 9 12 575V 690V Figure 9 3 Altitude Derating Curve Figure 9 4...
Page 281: ...Chapter 09 Specifications CP2000 9 16 9 8 Efficiency Curve Figure 9 11 Figure 9 12...
Page 317: ...Chapter 10 Digital Keypad CP2000 10 36 This page intentionally left blank...
Page 361: ...Chapter 11 Summary of Parameter Settings CP2000 11 44 This page intentionally left blank...
Page 416: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 3 3 4 5...
Page 417: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 4 6 7 8...
Page 418: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 5 9 10 11...
Page 419: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 6 12 13 14...
Page 420: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 7 15 16 17...
Page 421: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 8 18 19 20...
Page 422: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 9 21 22 23...
Page 423: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 10 24 25 26...
Page 424: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 11 27 28 29...
Page 425: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 12 30 31 32...
Page 426: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 13 33 34 35...
Page 427: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 14 36 37 38...
Page 836: ...Chapter 16 PLC Function Applications CP2000 16 153...
Page 838: ...Chapter 16 PLC Function Applications CP2000 16 155...
Page 841: ...Chapter 16 PLC Function Applications CP2000 16 158 This page intentionally left blank...
Page 857: ...Chapter 17 Introduction to BACnet CP2000 17 16 This page intentionally left blank...