D-700 MK3 User Manual Firmware V-16.8
- 39 -
Measurement method:
True RMS
Sampling rate:
8000 Hz
Harmonic analysis:
up to 31th harmonic
Supported topologies:
3 ph 4 wires star, 3 ph 4 wires delta,
3 ph 3 wires delta
3 ph 3 wires delta L1-L2
3 ph 3 wires delta L2-L3
2ph 3 wires L1-L2
2ph 3 wires L1-L3
1 ph 2 wires
CT secondary rating:
5A
Measurement range:
5/5 to 5000/5A minimum
Input impedance:
15 milliohm
Burden:
0.375W
Maximum continuous current:
6A
Measurement range:
0.1 to 7.5A
Common mode offset:
Max 5VAC between BAT- and any CT terminal.
Display resolution:
1A
Accuracy:
0.5% + 1 digit @ 5A (± 4.5A @ 5/500A full range)
4.4. 3 X MAINS CT INPUTS MODULE
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...