D-700 MK3 User Manual Firmware V-16.8
- 85 -
STATUS LEDS:
AUTO READY
: Turns on when the AUTO mode is selected and there is no condition preventing
engine start.
ALARM:
Turns on when a shutdown alarm or loaddump condition exists.
WARNING:
Turns on when a warning condition exists
SERVICE REQUEST:
Turns on when at least one of the service counters has expired.
PROGRAMMABLE LEDS:
2 leds reserved for customer specific use. Any alarm condition or input
function can be freely assigned to each led.
MODE LEDS:
Each led turns on when the related mode is selected, either locally or remotely.
MIMIC DIAGRAM LEDS:
MAINS AVAILABLE:
This led turns on when all mains phase voltages and the mains frequency
are within limits. If enabled, the mains phase rotation order must be also right. When any digital
input is defined as Remote Start, this led will reflect the status of the input. When a Simulate
Mains signal is present, then mains status will become “available”. When a Force to Start signal is
present, then the mains status will
become “not available”.
MAINS CONTACTOR ON:
Turns on when the mains contactor is activated.
GENSET CONTACTOR ON:
Turns on when the genset contactor is activated.
GENSET AVAILABLE:
This led turns on when all genset phase voltages and the genset
frequency are within limits. If enabled, the genset phase rotation order must be also right.
If a Remote Start input is defined, then the Mains led will
reflect the input status.
Simulate Mains and Force to Start signals will also affect this
led.
10.6. LED LAMPS
AUTO READY
indicator
Shutdown
alarm indicator
TEST mode
indicator
MANUAL
mode indicator
STOP mode
indicator
RUN mode
indicator
Programmable
LED indicators
AUTO mode
indicator
Mains
available led
Mains
Contactor
On led
Genset
available led
Genset
Contactor
on led
Warning
indicator
Service
request
indicator
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...