D-700 MK3 User Manual Firmware V-16.8
- 18 -
Supply voltage:
9 to 36VDC
Cranking dropouts:
Survives 0VDC during 100ms. The voltage before surge should be
9VDC minimum
Overvoltage protection:
Withstands 150VDC continuously.
Reverse voltage:
-36VDC continuous
Maximum operating
current:
600mA @ 12VDC. (All options included, digital outputs open.)
300mA @ 24VDC. (All options included, digital outputs open.)
Typical operating current:
300mA @ 12VDC. (all options passive, digital outputs open)
150mA @ 24VDC. (all options passive, digital outputs open)
Measurement range:
0 to 36VDC
Display resolution:
0.1VDC
Accuracy:
0.5% + 1 digit @ 24VDC
3.1. BATTERY VOLTAGE INPUT