D-700 MK3 User Manual Firmware V-16.8
- 209 -
In a manual genset, it is possible to reduce the current consumption of the unit down to true zero
Amperes, in order to prevent the battery from discharging.
For “zero power at rest operation”, an external relay and “wake-up” pushbutton is necessary.
A digital output should be set to ZERO POWER RELAY function. An external relay should be driven with
this digital output. The relay contact will feed the controller power supply.
Any digital output may be assigned as zero-power-relay output. Please refer to the relay function list for
the setup.
CONTROLLER
BAT+
OUTx
SUPPLY
The controller wakes-
up on applying the power through the “wake-up” pushbutton. Then it will
immediately activate the zero power output which will cause the zero power relay to feed the controller.
If the engine is not run, or if the engine stops, a timer of 5 minutes will be counted. At the expiration of the
counter, the controller will deenergize the zero power relay which will cut the power supply. The controller
will wait in a zero-power state until the wake-up pushbutton is depressed again.
36.24. ZERO POWER AT REST
Wake-Up
pushbutton
Zero Power
Relay
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...