D-700 MK3 User Manual Firmware V-16.8
- 160 -
The unit offers a programmable IDMT protection function in order to protect the alternator against excessive
currents.
The IDMT (Inverse Definite Minimum Time) protection function has such tripping characteristics that the
tripping time varies inversely with the value of current. Beyond a certain current limit the tripping time
becomes constant (definite) and causes tripping in minimum time.
The tripping formula is defined as below:
Where:
TMS
is the IDMT time multiplier setting. This is also the tripping time at 100% overload.
I
is the current of the most loaded phase
I
set
is the programmed overcurrent limit
t
is the tripping time in seconds
Currents below the overcurrent limit are allowed to flow for unlimited time. Currents above the limit will cause
the IDMT protection to trigger with a delay depending on the strength of the overcurrent. Higher the current,
faster the protection will trip.
When a non-tripping overcurrent condition occurs, the unit will keep trace of it. In case of a consecutive
overcurrent, the controller will take into account the residual heat caused by the previous overcurrent and will
trip faster than usual.
The IDMT multiplier adjusts the sensitivity of the IDMT detector. When the multiplier is low, then tripping will
be faster for the same current.
The unit provides separate Overcurrent limits for primary, secondary and tertiary volt/speed/amp settings.
Switching from primary volt/freq/amps to secondary or tertiary values will also switch the IDMT detector to
the secondary/tertiary setting.
The action of the tripping may be selected as a Loaddump (stop after cooldown) or shutdown alarm
(immediate stop).
Screenshot from RainbowPlus configuration program,
Generator>Current
section
22. OVERCURRENT PROTECTION (IDMT)
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...