D-700 MK3 User Manual Firmware V-16.8
- 77 -
Alternator voltage:
0 to 300 V-AC (Ph-N)
Alternator frequency:
0-600 Hz.
Mains voltage:
0 to 300 V-AC (Ph-N)
Mains frequency:
0-600 Hz.
Topology:
1-2-3 phases, with or without neutral
DC Supply Range:
8.0 to 36.0 V-DC.
V-A-cos Accuracy:
0.5% + 1 digit
kW-kVA-kVAr Accuracy:
1.0% + 1 digit
Current consumption:
500 mA-DC max.
Current Inputs:
from current transformers. ../5A or ../1A.
Digital inputs:
input voltage 0 to 36 V-DC.
Analog input range:
0-5000 ohms.
Mains and genset contactor outputs:
16Amps@250V
DC Outputs:
Protected mosfet semiconductor outputs, rated 1Amp@28V-DC
Cranking dropouts:
survives 0V for 100ms.
Magnetic pickup voltage:
0.5 to 50Vpk.
Magnetic pickup frequency:
0 to 20000 Hz.
Charge Alternator Excitation:
2W.
Display Screen:
4.3”, 480x272 pixels, color
Ethernet Port:
10/100 Mbits
USB Device:
USB 2.0 Full speed
USB Host:
USB 2.0 Full speed
RS-485 Port:
selectable baud rate (2400-115200baud)
Operating temperature:
-
20°C to 70°C (-4 to +158 °F)
Storage temperature:
-
40°C to 80°C (-40 to +176°F)
Maximum humidity:
95% non-condensing.
IP Protection:
IP65 from front panel, IP30 from the rear (with gasket)
Dimensions:
245 x 188 x 36mm (WxHxD)
Panel Cut-out Dimensions:
216 x 156 mm minimum.
Weight:
800 g (approx.)
Case Material:
High Temperature, non-flammable ABS/PC
Installation
:
Flat surface mounting on a Type 1 enclosure. Rear retaining plastic brackets.
EU Directives Conformity
-2014/35/EC (low voltage)
-2014/30/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
UL & CSA Compatibility:
• UL 6200, Controls for Stationary Engine Driven Assemblies (File# - 20140725-E314374)
• CAN/CSA C22.2 No. 14-13 – Industrial Control Equipment
9. TECHNICAL SPECIFICATIONS
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...