D-700 MK3 User Manual Firmware V-16.8
- 211 -
Modbus Slave Address:
may be set between 1 and 240
RS-485 Enable:
must be set to 1 (or checkbox enabled)
RS-485 Baud Rate:
selectable between 2400 and 115200 bauds. All devices in the same network must
use the same Baud Rate.
Selecting a higher baud rate will allow faster communication, but will reduce the communication distance.
Selecting a lower baud rate will increase the communication distance, but will cause slower response
times.
Typically 9600 bauds will allow 1200m distance with special balanced 120 ohms cable.
Modbus Slave Address:
may be set between 1 and 240. If only one unit is available in the same IP
address, it is advised to keep the default address (1).
Ethernet Enable:
This parameter should be set to 1 (or checked) in order to enable the ethernet port.
Modbus TCP/IP Port:
The usual setting is 502. However the unit is able to work on any port address.
User IP Mask:
There are 3 mask registers available. The use of the registers are emphasized in the
D700 User Manual. Please set the first mask as 255.255.255.0 for the proper operation.
Ethernet Network IP:
May be left as 0.0.0.0 for automatic address claim or set to a value in order to
claim a defined address.
Ethernet Gateway IP:
Should be set in accordance with your local switch configuration.
Ethernet Subnet Mask:
Should be set in accordance with your local switch configuration.
16bit variables:
These variables are stored in a single register. Bit_0 denotes the LSB and bit 15
denotes the MSB.
32 bit variables:
These variables are stored in 2 consecutive registers. The high order 16 bits are in the
first register and the low order 16 bits are in the second register
Bit arrays:
Arrays larger than 16 bits are stored in multiple registers. The LSB of the first register is bit_0.
The MSB of the first register is bit_15. The LSB of the second register is bit_16. The MSB of the second
register is bit_31, and so on.
37.3. DATA FORMATS
37.2. PARAMETERS REQUIRED FOR MODBUS-TCP/IP VIA ETHERNET
37.1. PARAMETERS REQUIRED FOR RS-485 MODBUS OPERATION
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...