SELECTING THE CT ACCURACY CLASS:
The CT accuracy class should be selected in accordance with the required measurement precision. The
accuracy class of controller is 0.5%. Thus 0.5% class CTs are advised for the best result.
CONNECTING CTs:
Be sure of connecting each CT to the related phase input with the correct polarity. Mixing CTs between
phases will cause faulty power and pf readings.
Many combinations of incorrect CTs connections are possible, so check both order of CTs and their
polarity. Reactive power measurement is affected by incorrect CTs connection in similar way as active
power measurement.
CORRECT CT CONNECTIONS
Let’s suppose that the genset is loaded with 100 kW on each phase. The load Power Factor (PF) is 1.
Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
100.0
0.0
100
1.00
Phase L3
100.0
0.0
100
1.00
Total
300.0
0.0
300
1.00
➢
Current Transformers must be used for current
measurement. No direct connection allowed.
➢
No common terminals or grounding allowed.
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...