D-700 MK3 User Manual Firmware V-16.8
- 188 -
The Peak Lopping feature consists on the use of the genset system as a backup to the mains, in cases
where the mains power rating is insufficient to supply the load.
When peak lopping is enabled and the unit is in
AUTO
mode, if mains power exceeds the parameter
Peak Lopping Start Power
during
Peak Lopping Start /Stop Delay,
then the genset system will start
and enter in parallel with the mains. As the mains power limit is not exceeded it will not supply power to
the load.
When the total load power exceeds the parameter
Peak Lopping Maximum Mains Power
the unit will
allow the mains to deliver only
Peak Lopping Maximum Mains Power
to the load. The exceeding
quantity will be supplied by the genset system.
When the total load power falls below the parameter
Peak Lopping Stop Power
during peak lopping
start/stop delay
Peak Lopping Start /Stop Delay
the load contactor will release and the unit swill start
the stop sequence.
The parameter
Peak Lopping Stop Power
should be less than the parameter
Peak Lopping Start
Power
in order to prevent unstable operation (genset starts and stops repeatedly).
The unit offers a comprehensive set of protection functions to detect quickly a mains failure during parallel
operation with mains. The protections are enabled after the timeout defined by the parameter
Parallel
Check Delay
. These protections will be explained with more detail in the chapter
G59 PROTECTIONS
.
If a
mains failure
occurs during parallel operation with mains, the mains contactor will immediately de-
energize, a general
Parallel Mains Fail
warning and a specific protection function warning will be
generated. The load will be supplied by the multi genset system without interruption. When mains is
restored again, the D700 will synchronize the genset system with the mains and resume to parallel
operation.
The D700 has a set of programmable parameters to define the Peak Lopping operation. All parameters
used in Uninterrupted
Transfer and Soft transfer are also used in Peak Lopping. Additional parameters
are:
Parameter Definition
Description
Peak Lopping Enable
This parameter enables/disables the Peak Lopping operation.
Peak Lopping Maximum
Mains Power
This is maximum active power that the mains may deliver.
Peak Lopping Start Power
This is the mains active power limit for the start of the multi genset
system.
Peak Lopping Stop Power This is the total load active power for the stop of the multi genset system.
Peak Lopping Start /Stop
Delay
This is the delay time for starting/stopping of the multi genset system.
The peak lopping may be disabled momentarily with an external signal. In order to achieve this, a digital
input should be programmed as
Disable Peak Lopping
function input. More information about input
programming is found in the
PROGRAMMING
chapter.
The peak lopping application is only possible with slowly varying
loads.
33.1. PEAK LOPPING
33. PARALLEL OPERATION WITH MAINS
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...