D-700 MK3 User Manual Firmware V-16.8
- 154 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Nominal Boost Voltage
V
6.0
60.0
28.8
This is the max charging voltage
allowed during the boost cycle.
Stop Current Percent
%
0
90
0
If this value is different from
zero
, when
the charge current falls below this
percentage of the max charge current,
then the charge cycle will be supposed
to be terminated.
If this parameter is set to
zero
, the
controller will monitor the charge current
automatically. When the charge current
is stabilized in a 5 minute interval, it will
conclude that the charge cycle is
terminated.
Idle Speed RPM
rpm
0
4000
900
This is the engine speed in IDLE
SPEED mode. This speed is maintained
with PID control.
RPM High Limit
rpm
750
8000
2000
This is the maximum allowed rpm of the
engine during charge cycle. If the
engine speed approaches this limit, the
controller will stop increasing the
current.
Battery Bank Over
Current
A
1
2000
63
If the current goes above this limit,
during the period defined in
Overload
Timeout
then a
Overcurrent Load
Dump
alarm will be generated.
If this parameter is 0 then Overcurrent
check is disabled.
Battery Bank Over Load
kw
0.1
200.0
1.6
If the active power goes above this limit,
during the period defined in Overload
Timeout then an
Excess Power Load
Dump
alarm will be generated.
If this parameter is 0 then Excess Power
check is disabled.
Alarm Warning Timer
sec
0
10
1
This is the period between the current or
active power go over the limits and
OVERCURRENT
or
EXCESS POWER
Load Dump alarms occur.
This is also the period between the
engine rpm goes out of the limits and
OVERSPEED
or
UNDERSPEED
alarms
occur.
This is also the period between the
alternator voltage goes out of the limits
and
HIGH VOLTAGE
or
LOW
VOLTAGE
alarms occur.
Genset Low Voltage
Shutdown Limit
V
0.0
460.0
9.0
If the battery bank DC voltage goes
under this limit, this will generate a
GENSET LOW VOLTAGE
shutdown.
Genset High Voltage
Warning Limit
V
0.0
460.0
63.0
If the battery bank DC voltage goes
above this limit, this will generate a
GENSET HIGH VOLTAGE
warning.
Genset High Voltage
Shutdown Limit
V
0.0
460.0
66.0
If the battery bank DC voltage goes
under this limit, this will generate a
GENSET HIGH VOLTAGE
alarm and
the engine will stop.
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...