D-700 MK3 User Manual Firmware V-16.8
- 54 -
The same unit provides different functionalities through parameter setting. Thus, a single stock item will
fulfill various duties, minimizing stock cost.
The selection of the functionality is done through Controller Parameter, as shown in below picture.
CTs may be placed at alternator or load sides. The CT location selection is configured with
Controller
Configuration > CT Location
parameter. When CTs are located at the alternator side, then mains
current and power parameters will not be displayed. When CTs are located at load side, then both mains
and genset currents and power parameters will be displayed, based on contactor positions. Please review
AMF functionality connection diagrams for CT connection details.
6.1. CT LOCATION SELECTION
6. FUNCTIONALITIES
Controller
Configuration
Parameters
Selection of
Functionality
CT Location
Selection
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...