D-700 MK3 User Manual Firmware V-16.8
- 163 -
MCB modules can be operated by 2 different ways. The unit supports both configurations.
Below is the terminology used:
M:
gear motor
PF:
ready to close contact
XF:
close coil
MX:
open coil
MN:
undervoltage trip (release)
AUX:
auxiliary contacts
MCB WITH OPEN-CLOSE COILS
MCB WITH CLOSE-UV COILS
In the diagram at left, relay function assignments should be as below:
OUTx:
Mains (or Genset) Close Pulse
OUTy:
Mains (or Genset) Open Pulse
In the diagram at right, relay function assignments should be as below:
OUTx:
Mains (or Genset) Close Pulse
OUTy:
Mains (or Genset) Undervoltage Coil