D-700 MK3 User Manual Firmware V-16.8
- 162 -
The unit offers full control for any brand and model of motorized circuit breakers (MCB).
The MCB control is performed through 3 digital output functions, namely Open, Close and Undervoltage coil
controls. Only 2 of these outputs are used in a single application.
Any digital output can be assigned to MCB control signals through programming menu.
The MCB CLOSE sequence is below:
Activate UV output, wait for undervoltage coil timer (t
uv
)
Activate CLOSE output, wait for close pulse timer (t
cl
)
Deactivate CLOSE output
The MCB OPEN sequence is below:
Deactivate UV output
Activate OPEN output, wait for open pulse timer (t
op
)
Deactivate OPEN output
If MCB feedback input is defined and the MCB fails to
change position after the expiration of MCB Fail timer,
then a fault condition will occur.
Open Pulse, Close Pulse and Undervoltage Coil timers
are adjusted through programming menu.
23. MOTORIZED CIRCUIT BREAKER CONTROL
Summary of Contents for D-700 MK3
Page 50: ...D 700 MK3 User Manual Firmware V 16 8 50 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR...
Page 64: ...D 700 MK3 User Manual Firmware V 16 8 64 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY...
Page 65: ...D 700 MK3 User Manual Firmware V 16 8 65 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT...
Page 66: ...D 700 MK3 User Manual Firmware V 16 8 66 7 4 DC GENSET FUNCTIONALITY...
Page 67: ...D 700 MK3 User Manual Firmware V 16 8 67 7 5 AMF FUNCTIONALITY...
Page 68: ...D 700 MK3 User Manual Firmware V 16 8 68 7 6 ATS FUNCTIONALITY...
Page 69: ...D 700 MK3 User Manual Firmware V 16 8 69 7 7 REMOTE START FUNCTIONALITY...
Page 70: ...D 700 MK3 User Manual Firmware V 16 8 70 7 8 ENGINE CONTROL FUNCTIONALITY...
Page 71: ...D 700 MK3 User Manual Firmware V 16 8 71 7 9 REMOTE DISPLAY PANEL FUNCTIONALITY...