DataDirect Networks EF2800 FC RAID Storage System User Guide (V 1.0)
T r o u b l e s h o o t i n g a n d P r o b l e m S o l v i n g
10.7.1
Power Supply/Cooling Modules
10.7.1.1
Removing the Module
If a power supply unit or its fan has failed, you must replace the whole
power supply/cooling module. As there should always be two power
supply units installed, you can continue working while replacing the
faulty module.
1.
Make sure you identify the faulty power supply/cooling module
correctly, from the two modules installed,
2.
Switch off and disconnect the power supply cord.
3.
Squeeze the two latches on the PSU handle together
(Figure 66)
.
4.
Pull and swing open the handle to cam the module out of the bay.
5.
Grip the handle and pull out the module.
Do not remove covers from the power supply unit.
Danger of electric shock inside. Return the PSU to your
supplier for repair.
!
Warning
Do not remove the faulty module unless you have a
replacement unit of the correct type ready for insertion.
!
Warning
Figure 66. Disengage the Latches on PSU Module
Summary of Contents for EF2800
Page 1: ...EF2800 Fibre Channel RAID System User Guide ...
Page 2: ...V 1 0 EF2800 Fibre Channel RAID Storage System User Guide DataDirect Networks ...
Page 5: ...iv This page intentionally left blank ...
Page 13: ...This page intentionally left blank xii ...
Page 37: ...This page intentionally left blank 14 ...
Page 65: ...This page intentionally left blank 42 ...
Page 79: ...This page intentionally left blank 56 ...
Page 201: ...This page intentionally left blank 178 ...
Page 215: ...This page intentionally left blank 192 ...
Page 227: ...This page intentionally left blank 204 ...
Page 305: ...This page intentionally left blank 282 ...
Page 343: ...This page intentionally left blank 320 ...