Technical item or function
Technical data
Switching frequency (see param-
eter P2.6.9)
208–240 V and 380–500 V, up to 0061: 1–16 kHz
Default: 6 kHz
208–240 V, 0075 and larger: 1–10 kHz
Default: 3.6 kHz
380–500 V, 0072 and larger: 1–6 kHz
Default: 3.6 kHz
525–690 V: 1–6 kHz
Default: 1.5 kHz
Frequency reference
Analog input
Panel reference
Resolution 0.1% (VACON
®
NXP: 12-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point
8–320 Hz
Acceleration time
0.1–3000 s
Deceleration time
0.1–3000 s
Brake power
DC brake: 30% * TN (without the brake option)
Ambient conditions
Ambient operating temperature
FR4-FR9 I
L
current:
-10 °C (-14 °F) (no frost)...+40 °C (104 °F)
I
H
current: -10 °C (-14 °F) (no frost)...+50 °C (122 °F)
FR10-FR11 Standalone (IP21/UL Type 1)
I
H
/I
L
: –10 °C (-14 °F) (no frost)…+40 °C (104 °F) (except 525–690 V,
0461 and 0590: –10 °C (-14 °F) (no frost)… +35 °C (95 °F))
FR10 Standalone (IP54/UL Type 12)
I
H
/I
L
: –10 °C (-14 °F) (no frost)…+40 °C (104 °F) (except 380–500 V,
0520, and 525–690 V, 0416: –10 °C (-14 °F) (no frost)…+35 °C (95 °F))
For higher ambient temperatures see Motor connection – Continuous
output current in this table.
Storage temperature
-40 °C (-104 °F)...+70 °C (158 °F)
Relative humidity
0–95% RH, non-condensing, non-corrosive, no dripping water
Altitude
100% load capacity (no derating) up to 1000 m (3281 ft) 1% derating
for each 100 m (328 ft) above 1000 m (3281 ft)
AQ275638903263en-000601 / DPD00910
164 | Danfoss A/S © 2022.12
Specifications
VACON® NXS/NXP Air-cooled
Operating Guide